Egress Window Requirements in Ontario: size, code and wells

If a bedroom sits on a floor level, Ontario requires a way out of that level besides the stairs. In a basement, that almost always means an egress window. This guide gives you the actual numbers from the Ontario Building Code, the different numbers the Fire Code uses for existing basement apartments, and the window-well and permit rules that trip up most homeowners.

We have cut and installed more than 1,000 egress windows across Toronto, the GTA, Hamilton and Kitchener-Waterloo, and every one of them had to pass the same inspection. What follows is what inspectors actually check.

The short answer: OBC 9.9.10.1

For a floor level that contains a bedroom, at least one outside window on that level must:

0.35 m² clear openingAbout 3.77 sq ft, measured on the open portion of the window, not the glass or the frame.
No side under 380 mmThat is 15 inches. A 15 in by 36¼ in opening passes. A 15 in by 15 in opening does not.
Opens without tools or keysFrom the inside, without special knowledge, and it must stay open on its own.
550 mm clear in the window wellAbout 22 inches between the open window and the well wall, so a person can climb out.
One per floor levelOntario asks for one compliant window or exterior door per floor level with a bedroom, not one per bedroom.
Sill heightThe Code sets a 1,000 mm limit above the floor, with an exception for basements. Lower is safer and easier to pass.

Source: Ontario Building Code, Division B, Article 9.9.10.1, as interpreted in municipal building-department advisories (City of Ottawa, Aug 2025).

Who the rule applies to

Article 9.9.10.1 applies to every floor level in a house that contains a bedroom. The trigger is the bedroom, not the basement. A finished basement with a home office or rec room does not need an egress window under this article. Put a bed and a closet down there and call it a bedroom, and it does.

Two exceptions matter. If the floor level has a door that opens directly to the outside, that door counts as the egress and a window is not required. And if the house is protected by a sprinkler system, the requirement is waived. Almost no Ontario houses are sprinklered, so for practical purposes a basement bedroom means a compliant window or a walkout door.

Note the wording: one per floor level. The National Building Code asks for one per bedroom, and a lot of online guides copy that rule. Ontario does not. If you have two basement bedrooms, one compliant egress window on that level satisfies the Building Code, although some municipalities and most fire inspectors will push for a window in each sleeping room when you register a second unit. Ask us or your building department before you assume one is enough.

What 0.35 m² actually means for window size

The area is the clear opening: the hole a person can actually pass through when the window is fully open. It is not the size of the glass and it is not the rough opening in the wall. Frame, sash and hardware all eat into it, and how much they eat depends on the window type.

  • Casement (side-hinged, cranks open). The whole sash swings clear, so the clear opening is close to the frame size. A standard 30 in by 30 in brick opening with a casement passes comfortably. This is the most common egress window we install.
  • Tilt and turn. Opens inward like a door, so the full opening is available and nothing sticks out into the well. Popular where the well is tight or the window is at grade.
  • Slider. Only one half opens. To get 0.35 m² of clear opening from a slider, the window itself has to be roughly twice as wide, typically a 60 in by 24 in opening or larger. Most existing basement sliders fail this test.
  • Hopper and awning. The sash stays in the opening when tilted, so the clear area is a fraction of the frame. These almost never qualify as egress.

Three openings that meet the minimum, straight from the Code appendix: 380 mm by 920 mm (15 in by 36¼ in), 592 mm by 592 mm (23 5/16 in square), and 920 mm by 380 mm. Anything with the same or larger area, and no side under 380 mm, also passes.

Black casement egress window in a steel well, exterior view, Toronto
Casement egress window after a cut-down: the whole sash swings clear of the opening (Toronto).
Tilt and turn opens inward, so nothing projects into the well and the full opening is available.

EXPERT INSTALLATION & REPLACEMENT

Instant quotes
Call (647) 699-2371

Are you looking to enlarge windows in your home or business? Fill out this short form and we'll get back to you in less than 10 minutes.*

* Responses outside of regular business hours may take longer.

We respond in 10 minutes or less

    Sill height and what to do about a high window

    The Code limits the sill to 1,000 mm (about 39 in) above the floor, with an exception for basements, where the original window is often higher than that. The practical answer inspectors accept is fixed steps, a built-in cabinet or a platform under the window so the climb to the sill is 1,000 mm or less. Loose furniture does not count.

    In most of our projects the better fix is to cut the opening down: keep the same width, lower the sill, and install a taller window. You get the clear opening, a lower sill and far more daylight in one step, and a cut-down usually does not need a permit because the structure above the window is untouched.

    One more rule that catches people: any window with a sill below 900 mm needs a fall-prevention limiter under Article 9.8.8.1, but an egress window’s limiter must release without tools. Standard child-safety stoppers that need a screwdriver are not allowed on an egress window.

    Original small basement window in a block wall before an egress cut-down, Oshawa
    Before: the original block-wall window. Opening well under 0.35 m², sill above 1,000 mm (Oshawa).
    Finished egress window after a cut-down, with galvanized steel window well, Oshawa
    After the cut-down on the same house: sill lowered, casement window, galvanized steel well.

    Window well rules

    Below grade, the window opens into a well, and the well has its own requirements.

    • Clearance. At least 550 mm (22 in) between the fully open window and the well wall. Casement sashes swing into that space, so a casement needs a deeper well than a tilt and turn.
    • Depth. Where the well is deeper than 1,000 mm, the building department will expect a way to climb out: a ladder or steps built into the well.
    • Drainage. Not an egress rule, but the reason wells fail. The well needs a gravel base tied into the weeping tile or a drain, or it fills with water and the window leaks. See our window well installation page.
    • Covers. A well cover is allowed and we recommend one, but it must open from inside without tools. Bolted or padlocked covers turn an egress window into a non-compliant one.
    Steel well with a gravel drainage base. The 550 mm clearance is measured from the open sash to the well wall.
    Professional window well installation showing black egress window with steel well and gravel drainage base
    Clear polycarbonate cover: keeps leaves and water out and lifts from inside without tools.

    Building Code vs Fire Code: two sets of numbers

    Homeowners get two different size rules quoted at them, and both are correct. They come from different laws.

    ServiceTypical Price Range
    Ontario Building Code 9.9.10.1New construction, renovations under a building permit, new secondary suites.0.35 m² · min 380 mm · 550 mm well
    Ontario Fire Code 9.8.3.4Retrofit of an existing two-unit house (registering an existing basement apartment).0.38 m² · min 460 mm · 1 m well
    Fire Code casement alternativeCasement at least 1,060 mm high by 560 mm wide, sill no more than 900 mm above the floor.1,060 × 560 mm

    Fire Code escape windows also require the sill to be no more than 900 mm above the floor or fixed steps, and no more than 1 m above or below grade.

    Which one applies to you? If you are pulling a building permit to create a suite or cut a new opening, the building inspector uses the Building Code. If a fire prevention officer is inspecting an existing second unit, they use Fire Code Section 9.8. When there is any chance of both, we build to the larger Fire Code numbers so the window passes either inspection.

    Do you need a permit?

    Cutting a new opening or widening an existing one in a foundation wall is structural work and needs a building permit in every Ontario municipality. The application needs drawings showing the opening, the lintel or header above it and the well. Some cities ask for an engineer’s letter for wider openings. There is an inspection when the work is done.

    A cut-down, lowering the sill without changing the width, usually does not need a permit because the load path above the window does not change. Replacing a window with the same size never does.

    If the egress window is part of a legal secondary suite, the suite itself needs a permit, and the window is reviewed as part of it. We prepare the drawings, submit the application and meet the inspector on every permitted job. Our work is guaranteed to pass inspection; if the inspector flags our workmanship, we fix it at no cost.

    Steel lintel being set above a new egress opening in a block foundation, Burlington
    Steel lintel set above a new opening in a block foundation, exactly what the permit drawings describe (Burlington).
    Egress window with pressure-treated wood window well, Whitby
    Finished full cut with a pressure-treated well, ready for the inspector (Whitby).

    Mistakes we get called in to fix

    • Measuring the frame or the glass instead of the clear opening. A 30 in slider looks big and fails.
    • Installing a slider or hopper in an opening that only a casement or tilt and turn could make compliant.
    • A well that touches the open sash, leaving less than 550 mm to climb through.
    • A cover screwed down from outside, or a security bar across the opening.
    • A sill so high that only a chair makes the window reachable.
    • No drainage under the well, so the first spring thaw floods the new bedroom.
    • Two bedrooms registered as a second unit with a single small window that meets the Building Code but not the Fire Code.

    Every one of these means opening the wall a second time. Getting the size, the window type and the well right the first time is the entire job.

    Check your existing basement window in five minutes

    1. Open the window as far as it goes. If you need a key, a tool or two hands and a trick, stop: it fails.
    2. Measure the clear width and clear height of the opening you could pass through, in inches.
    3. Multiply them. You need at least 543 square inches (0.35 m²), and neither number can be under 15 in.
    4. Measure from the open sash to the well wall. You need 22 in or more.
    5. Measure from the floor to the sill. Over 39 in means steps or a cut-down.

    If any step fails, send us two photos, one from inside and one from outside, and we will tell you which fix applies and what it costs. Typical installed prices are on our egress window cost page.

    Get a free on-site assessment

    Egress Window Requirements FAQ

    Under the Ontario Building Code, one compliant egress window or exterior door per floor level that contains a bedroom is the minimum. Fire inspectors registering an existing second unit often require a window in each sleeping room, so if the basement is or will be an apartment, plan for one per bedroom.

    A clear opening of at least 0.35 square metres (about 3.77 square feet) with no dimension less than 380 mm (15 inches), openable from inside without tools. If the window opens into a well, the well must give at least 550 mm of clearance in front of the window.

    Only if it is large. Half of a slider is fixed, so the clear opening is roughly half the frame width. You generally need a slider around 60 inches wide by 24 inches tall to reach 0.35 m². Most egress projects use a casement or tilt-and-turn window instead.

    Yes, as long as the cover can be opened from inside the well without tools or keys. Covers that are bolted, screwed or locked from outside make the window non-compliant.

    Cutting a new opening or widening an existing one in a foundation wall needs a building permit everywhere in Ontario. Lowering the sill without changing the width, a cut-down, usually does not. We confirm this for your municipality and handle the permit when one is needed.

    The Building Code (0.35 m², 380 mm) governs new work under a building permit. Fire Code Section 9.8 (0.38 m², 460 mm, 1 m well clearance) is the retrofit standard applied to existing two-unit houses. When both could apply, build to the larger Fire Code numbers.